Hospital clean room is mainly used in modular operation room, ICU, isolation room, etc. Medical clean room is a huge and special industry, especially modular operation room has high requirement on air cleanliness. Modular operation room is the most important part of hospital and it consist of main operation room and auxiliary area. The ideal cleanliness level near operation table is to reach class 100. Usually recommend hepa filtered laminar flow ceiling at least 3*3m at top, so operation table and operator can be covered inside. The patient infection rate in sterile environment can reduce more than 10 times, so it can less or not use antibiotics to avoid damaging human immune system.
Room | Air Change
(Times/h) |
Pressure Difference in Adjacent Clean Rooms | Temp. (℃) | RH (%) | Illumination(Lux) | Noise (dB) |
Special Modular Operation Room | / | 8 | 20-25 | 40-60 | ≥350 | ≤52 |
Standard Modular Operation Room | 30-36 | 8 | 20-25 | 40-60 | ≥350 | ≤50 |
General Modular Operation Room | 20-24 | 5 | 20-25 | 35-60 | ≥350 | ≤50 |
Quasi Modular Operation Room | 12-15 | 5 | 20-25 | 35-60 | ≥350 | ≤50 |
Nurse Station | 10-13 | 5 | 21-27 | ≤60 | ≥150 | ≤60 |
Clean Corridor | 10-13 | 0-5 | 21-27 | ≤60 | ≥150 | ≤52 |
Change Room | 8-10 | 0-5 | 21-27 | ≤60 | ≥200 | ≤60 |
Q: What cleanliness is in modular operation theatre?
A: It is usually ISO 7 cleanliness required for its surrounding area and ISO 5 cleanliness above operation table.
Q: What content is included in your hospital clean room?
A: There are mainly 4 parts including structure part, HVAC part, eletrical part and control part.
Q: How long will medical clean room take from initial design to final operation?
A: It depends on the work scope and usually it can be finished within one year.
Q: Can you do overseas clean room installation and commissioning?
A: Yes, we can arrange if you require.